RetroSenseBehind the Signals
Back to the app

In one sentence

Old pumps, the sensors they already have, and a clear answer.

RetroSense tells the operator early what is wrong, what to do, and when not to trust a reading. It only reads data; people act, and the plant’s own alarms stay in charge.

Results · organizer’s own scorer

Score, training pumps

94.0

baseline 58.2

Score, validation pumps

85.4

baseline 78.0

False alerts per pump per day

0.06

training · baseline 0.12
validation 0.00 · baseline 0.07

Training pumps

Faults found
100%
69%
Fault named right
96%
27%
Pump or sensor right
100%
54%

Validation pumps

Faults found
89%
89%
Fault named right
78%
44%
Alerts that were real
100%
89%
RetroSenseOrganizer’s baseline (B1)

Every setting was chosen on training pumps only. Official organizer scorer. Settings chosen on training pumps only; validation scored once. Validation has 2 pumps and 9 events, so a few points either way is noise.

What a fixed alarm can’t do

01 · Pump or sensor

It tells a broken sensor from a broken pump

A reading moves but the signals that should move with it don’t: it’s the sensor. Check the transmitter, don’t stop the pump.

8 of 8sensor faults named as the sensor

02 · Cause, not symptoms

One cause, one action

A clogging strainer leads to cavitation. RetroSense links them, so the crew cleans the strainer instead of chasing alarms.

4 → 7of 7 cause chains shown

03 · Honest

Worn from day one? It still notices

With no healthy history, it compares the pump with the maker’s data sheet. Where sensors are missing, it says “can’t see”, never “healthy”.

2 → 3of 4 day-one faults named right

The five clues · training pumps

Five things the challenge asked us to catch

Before = our first complete version (score 86.8). Now = the final version (score 94.0). The number is how many of those faults were named right.

Cavitation and clogging

6 → 7 of 7

Fixed: one clogging strainer was first called a drifting gauge, because only suction moved clearly. Now RetroSense checks the pressure in kPa: when discharge falls with suction, it is the pump, not the gauge. It also flags cavitation after 5 minutes below the safe margin, so short episodes are caught.

Bearing wear

3 → 3 of 3

Already right: the bearing’s own defect frequency shows up in the vibration spectrum long before the overall vibration alarm. Nothing to fix; it stayed perfect while we changed the rest.

Sick on day one

2 → 3 of 4

Added: a pump worn from the first minute looks normal against its own history. We now also compare it with the maker’s pump curve, so no healthy first day is needed. Still open: a closed cooling loop has no suction reference, so that check can’t run; the screen says “can’t see” instead of guessing.

Sensor or machine

8 → 8 of 8

Already right: a reading that moves while the signals that should follow it don’t is the sensor. It stayed perfect while every other check was added.

Cause chains

6 → 7 of 7

Added: cards now carry their cause. Cavitation soon after clogging points back to the clogging, and a fault right after a repair points back to the repair (bearing replacement → misalignment).

Safe by design

Reads only, never writes

No path to the PLC, drive, valves or safety system.

Advisory

A person approves every action; every alert prints as a work card that starts with the local gauge.

Plant alarms and trips stay in charge

Designed with IEC 62443 principles in mind; to be assessed per site.

It checks its own sensors first

Faults injected into PUMP-01’s discharge pressure, 30 minutes.

Healthy sensor

No alarm

Frozen reading

10 min

to flag it

Noisy reading

5 min

to flag it

Hui’s controlled synthetic tests; not a measure of real-world accuracy.

What it could be worth

Illustrative

0.9 yr

payback, one duty pump

€4,905

net per year, one duty pump

never

payback, standby pump (€−2,037 / year)

Organizer’s own business-case model, run with our measured numbers. Synthetic data and assumed costs: start with duty pumps.

What we don’t claim

Synthetic data only

Nothing has run on a real plant yet. Next step: a few weeks in shadow mode.

Small validation set

Official organizer scorer. Settings chosen on training pumps only; validation scored once. Validation has 2 pumps and 9 events, so a few points either way is noise.

Not certified

Read-only installation and IEC 62443 alignment are proposed, to be assessed per site.